Calibration and Initialization of Electronic Remote Seal level transmitter -Rosemount 3051ERS

Electronic Remote Seal level transmitter -Rosemount 3051ERS

Initial setting of transmitter:

After installation of the transmitter, measure the tap to tap length of the H.P. side and L.P. side, here consider the level to be measured=the tap to tap measured length be 9000 mm, the LRV and URV can be calculated as follows

LRV=Value when the tank is filled with upper liquid of lower density=height of the tap to tap measurement*S.G. of upper liquid=9000*0.85=7650

URV=value when the tank is filled with lower liquid of higher density=Tap to tap measurement*S.G of the lower liquid=9000*1=9000

Calibration of the LT:

Fill the tank with water or the liquid with higher density then the transmitter should show 100%

Next fill the tank with liquid of lower density then the transmitter should show 0%